Functions Common to all the Control Modes
12-20 | CFW700
P0302 – DC-Braking Voltage
Adjustable
Range:
0.0 to 10.0 %
Factory
Setting:
2.0 %
Properties:
V/f and VVW
Access groups
via HMI:
Description:
This parameter adjusts the DC voltage (braking torque) applied to the motor during the braking.
The adjustment must be done by increasing gradually the P0302 value, which varies from 0 to 10 % of the rated
voltage, until getting the desired braking.
This parameter works only for the V/f scalar and VVW control modes.
P0372 – DC-Braking Current for Sensorless
Adjustable
Range:
0.0 to 90.0 %
Factory
Setting:
40.0 %
Properties:
Sless
Access groups
via HMI:
Description:
This parameter adjusts the current level (DC braking torque) applied to the motor during the braking.
The programmed current level is a percentage of the inverter rated current.
This parameter works only in the Sensorless Vector control mode.