Digital and Analog Inputs and Outputs
13
CFW700 | 13-9
13.1.3 Digital Inputs
The CFW700 has 8 digital inputs in the standard version. The parameters that configure those inputs are presented
next.
P0012 – DI8 to DI1 Status
Adjustable
Range:
Bit 0 = DI1
Bit 1 = DI2
Bit 2 = DI3
Bit 3 = DI4
Bit 4 = DI5
Bit 5 = DI6
Bit 6 = DI7
Bit 7 = DI8
Factory
Setting:
Properties:
ro
Access groups
via HMI:
READ or I/O
Description:
By means of this parameter it is possible to visualize the status of the 8 control board digital inputs (DI1 to DI8).
The indication is done by means of the numbers 1 and 0, representing respectively the “Active” and “Inactive”
states of the inputs. The state of each input is considered as one digit in the sequence where DI1 represents
the least significant digit.
Example: In case the sequence
10100010
is presented on the keypad (HMI), it will correspond to the following
status of the DIs:
Table 13.6:
Digital inputs status
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
Active
(+24 V)
Inactive
(0 V)
Active
(+24 V)
Inactive
(0 V)
Inactive
(0 V)
Inactive
(0 V)
Active
(+24 V)
Inactive
(0 V)
P0263 – DI1 Function
P0264 – DI2 Function
P0265 – DI3 Function
P0266 – DI4 Function
P0267 – DI5 Function
P0268 – DI6 Function
P0269 – DI7 Function
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...