Quick Parameter Reference, Faults and Alarms
0-10 | CFW700
Param.
Description
Adjustable Range
Factory Setting
User
Setting
Propr.
Grorps
Pag.
P0313
Communication Error Action 0 = Off
1 = Ramp Stop
2 = General Disable
3 = Goes to LOC
4 = LOC Keeping Enabled
5 = Causes Fault
0 = Off
NET
17-4
P0314
Serial Watchdog
0.0 to 999.0 s
0.0 s
NET
17-1
P0316
Serial Interface Status
0 = Off
1 = On
2 = Watchdog Error
ro
NET
17-1
P0317
Oriented Start-up
0 = No
1 = Yes
0 = No
cfg
10-6
11-29
P0318
Copy Function MMF
0 = Off
1 = VFD
→
MMF
2 = MMF
→
VFD
3 = VFD Synchronization
→
MMF
4 = MMF Format
5 = SoftPLC Program
Copy
0 = Off
cfg
7-2
P0320
FlyStart/Ride-Through
0 = Off
1 = Flying Start
2 = FS / RT
3 = Ride-Through
0 = Off
cfg
12-8
P0321
DC Link Power Loss
178 to 616 V
505 V
Vector
12-15
P0322
DC Link Ride-Through
178 to 616 V
490 V
Vector
12-15
P0323
DC Link Power Back
178 to 616 V
535 V
Vector
12-15
P0325
Ride-Through P Gain
0.0 to 63.9
22.8
Vector
12-16
P0326
Ride-Through I Gain
0.000 to 9.999
0.128
Vector
12-16
P0327
FS I/f Current Ramp
0.000 to 1.000 s
0.070
Sless
12-10
P0328
Flying Start Filter
0.000 to 1.000 s
0.085
Sless
12-10
P0329
FS I/f Frequency Ramp
2.0 to 50.0
6.0
Sless
12-10
P0331
Voltage Ramp
0.2 to 60.0 s
2.0 s
V/f and
V V W
12-12
P0332
Dead Time
0.1 to 10.0 s
1.0 s
V/f and
V V W
12-13
P0340
Auto-Reset Time
0 to 255 s
0 s
15-7
P0343
Ground Fault Configuration
0 = Off
1 = On
1 = On
cfg
15-8
P0344
Current Limit Configuration
0 = Hold - FL ON
1 = Decel. - FL ON
2 = Hold - FL OFF
3 = Decel.- FL OFF
1 = Decel. - FL ON
cfg, V/f
and V V W
9-7
P0348
Motor Overload
Configuration
0 = Off
1 = Fault/Alarm
2 = Fault
3 = Alarm
1 = Fault/Alarm
cfg
15-8
P0349
I x t Alarm Level
70 to 100 %
85 %
cfg
15-9
P0350
IGBT Overload Configuration 0 = F, w/ SF rd.
1 = F/A, w/ SF rd.
2 = F, no SF rd.
3 = F/A, no SF rd.
1 = F/A, w/ SF rd.
cfg
15-9
P0351
Motor Overtemperature
Config.
0 = Off
1 = Fault/Alarm
2 = Fault
3 = Alarm
1 = Fault/Alarm
cfg
15-10
P0352
Fan Control Configuration
0 = HS-OFF, Int-OFF
1 = HS-ON, Int-ON
2 = HS-CT, Int-CT
3 = HS-CT, Int-OFF
4 = HS-CT, Int-ON
5 = HS-ON, Int-OFF
6 = HS-ON, Int-CT
7 = HS-OFF, Int-ON
8 = HS-OFF, Int-CT
2 = HS-CT, Int-CT
cfg
15-10
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...