P0159 – Motor Tripping Class
Adjustable
Range:
0 = Class 5
1 = Class 10
2 = Class 15
3 = Class 20
4 = Class 25
5 = Class 30
6 = Class 35
7 = Class 40
8 = Class 45
Factory
Setting:
1
Properties:
cfg
Access groups
via HMI:
Description:
This parameter sets the motor thermal class, and the time for the correct actuation of the F072 fault depends
on it. The higher the thermal class, the longer the fault actuation time will be.
ATTENTION!
The incorrect selection of the thermal class may cause the burning of the motor.
ATTENTION!
In order the CFW700 motor overload protection is in accordance with UL508C, the thermal class
should be ≤20 (P0159 ≤ 3).
The necessary data for choosing the thermal class are the following:
Motor rated current (I
n
).
Blocked rotor current (I
p
).
Blocked rotor time (T
RB
)
(*)
.
Service factor (SF).
(*)
It must be verified if the given blocked rotor time is for hot or cold motor, so that the correspondent thermal
class curves be used.
With those values, the overload current and the overload time must be calculated using the following equations:
Overload Current =
I
p
x 100 (%)
I
n
x FS
Overload Time = T
BR
(s)
These equations provide the limit conditions for the error actuation, i.e., the motor cannot work with a longer fault
actuation time than this one, because of burning risk. Thus, a thermal class immediately inferior must be chosen
so that the motor protection is assured.
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...