10
VVW Control
10-4 | CFW700
P0400 – Motor Rated Voltage
P0401 – Motor Rated Current
P0402 – Motor Rated Speed
P0403 – Motor Rated Frequency
P0404 – Motor Rated Power
P0406 – Motor Ventilation
Refer to the
, for more information.
P0407 – Motor Rated Power Factor
Adjustable
Range:
0.50 to 0.99
Factory
Setting:
0.68
Properties:
cfg and VVW
Access groups
via HMI:
MOTOR
Description:
It is the motor power factor setting, according to the motor nameplate data (cos Ø).
This parameter is important for the VVW control operation. The inaccurate setting will imply in incorrect
calculation of the slip compensation.
The default value of this parameter is adjusted automatically when the parameter P0404 is changed. The
suggested value is valid for three-phase, IV pole WEG motors. For other motor types the setting must be done
manually.
P0408– Run Self-Tuning
P0409 – Motor Stator Resistance (Rs)
P0410 – Motor Magnetizing Current (I
m
)
Refer to
, for more information.