16
Read only Parameters
16-4 | CFW700
P0009 = Tm x 100 x Y
I
TM
I
TM
= P0401
2
-
P0410 x P0178
2
1/2
100
Y = 1 for N
≤
P0190 x N
nom
P0400
Y =
N
nom
x
P0190
for N >
P0190 x N
nom
N P0400 P0400
Where:
N
nom
= Motor synchronous speed.
N = Motor actual speed.
T
m
= Motor torque current.
I
TM
= Rated motor torque current.
P0010 – Output Power
Adjustable
Range:
0.0 to 6553.5 kW
Factory
Setting:
Properties:
ro
Access groups
via HMI:
READ
Description:
It shows the inverter instantaneous output power, in kilowatt (kW).
NOTE!
The value indicated in this parameter is calculated indirectly, and must not be used to measure the
energy consumption.
P0012 – DI8 to DI1 Status
Refer to
.
P0013 – DO5 to DO1 Status
Refer to item
13.1.4 - Digital Outputs / Relays
.
P0014 – AO1 Value
P0015 – AO2 Value
P0018 – AI1 Value
P0019 – AI2 Value