16
Read only Parameters
16-6 | CFW700
P0039 – Encoder Pulse Counter
Adjustable
Range:
0 to 40000
Factory
Setting:
Properties:
ro
Access groups
via HMI:
READ
Description:
This parameter shows the counting of the pulses of the encoder. The counting can be increased from 0 to
40000 (Hourly turn) or decreased from 40000 to 0 (rotate Counterclockwise).
P0042 – Powered Time
Adjustable
Range:
0 to 65535 h
Factory
Setting:
Properties:
ro
Access groups
via HMI:
READ
Description:
It indicates the total number of hours that the inverter remained powered.
This value is kept even when power is removed from the inverter.
P0043 – Enabled Time
Adjustable
Range:
0.0 to 6553.5 h
Factory
Setting:
Properties:
ro
Access groups
via HMI:
READ
Description:
It indicates the total number of hours that the inverter remained enabled.
It indicates up to 6553.5 hours, and then it gets back to zero.
By setting P0204=3, the value of the parameter P0043 is reset to zero.
This value is kept even when power is removed from the inverter.