Faults and Alarms
15
CFW700 | 15-11
The options available for the setting of this parameter are the following:
Table 15.5:
Options of the parameter P0352
P0352
Action
0 = HS-OFF, Int-OFF
Heatsink fan is always OFF.
Internal fan is always OFF.
1 = HS-ON, Int-ON
Heatsink fan is always ON.
Internal fan is always ON.
2 = HS-CT, Int-CT
Heatsink fan is controlled via software.
Internal fan is controlled via software.
3 = HS-CT, Int-OFF
Heatsink fan is controlled via software.
Internal fan is always OFF.
4 = HS-CT, Int-ON
Heatsink fan is controlled via software.
Internal fan is always ON.
5 = HS-ON, Int-OFF
Heatsink fan is always ON.
Internal fan is always OFF.
6 = HS-ON, Int-CT
Heatsink fan is always ON.
Internal fan is controlled via software.
7 = HS-OFF, Int-ON
Heatsink fan is always OFF.
Internal fan is always ON.
8 = HS-OFF, Int-CT
Heatsink fan is always OFF.
Internal fan is controlled via software.
P0353 – IGBTs/Air Overtemperature Configuration
Adjustable
Range:
0 = IGBTs: fault and alarm, Internal air: fault and alarm
1 = IGBTs: fault and alarm, Internal air: fault
2 = IGBTs: fault, Internal air: fault and alarm
3 = IGBTs: fault, Internal air: fault
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
Description:
The overtemperature protection is carried out by means of the measurement of the temperature with the IGBTs
and power board internal air NTCs, being able to generate alarms and faults.
In order to configure the desired protection, set P0353 according to the table below.
Table 15.6:
Options of the parameter P0353
P0353
Action
0 = HS-F/A, Air-F/A
Enables fault (F051) – IGBT Overtemperature and alarm (A050) – IGBT High Temperature.
Enables fault (F153) – Internal Air Overtemperature and alarm (A152) – High Internal Air Temperature.
1 = HS-F/A, Air-F
Enables fault (F051) and alarm (A050) for IGBTs overtemperature.
Enables only fault (F153) for internal air overtemperature.
2 = HS-F, Air-F/A
Enables only fault (F051) for IGBT overtemperature.
Enables fault (F153) and alarm (A152) for internal air overtemperature.
3 = HS-F, Air-F
Enables only fault (F051) for IGBT overtemperature.
Enables only fault (F153) for internal air overtemperature.
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...