Digital and Analog Inputs and Outputs
13
CFW700 | 13-23
P0221 – Speed Reference Selection – LOCAL Situation
P0222 – Speed Reference Selection – REMOTE Situation
Adjustable
Range:
0 = HMI
1 = AI1
2 = AI2
3 = AI1+AI2 > 0 (Sum AIs>0)
4 = AI1+AI2 (Sum AIs)
5 = Serial
6 = CANopen/DeviceNet/Profibus DP
7 = SoftPLC
Factory
Setting:
P0221=0
P0222=1
Properties:
cfg
Access groups
via HMI:
I/O
Description:
They define the origin of the Speed Reference in the LOCAL situation and in the REMOTE situation.
Some notes about the options for those parameters:
The AIx’ designation refers to the analog signal obtained after the addition of the AIx input to the offset and
its multiplication by the applied gain (refer to
).
The value of the reference adjusted with the
and
is contained in the parameter P0121.
P0223 – FORWARD/REVERSE Selection - LOCAL Situation
P0226 – FORWARD/REVERSE Selection - REMOTE Situation
Adjustable
Range:
0 = Forward
1 = Reverse
2 = Forward/Reverse Key (FWD)
3 = Forward/Reverse Key (REV)
4 = DIx
5 = Serial (FWD)
6 = Serial (REV)
7 = CANopen/DeviceNet/Profibus DP (FWD)
8 = CANopen/DeviceNet/Profibus DP (REV)
9 = SoftPLC (FWD)
10 = SoftPLC (REV)
11 = AI2 Polarity
Factory
Setting:
P0223=2
P0226=4
Properties:
cfg
Access groups
via HMI:
I/O
Description:
They define the origin of the “Speed Direction” command in the LOCAL situation and in the REMOTE situation,
where:
FWD: Means Forward Default situation.
REV: Means Reverse Default situation.
DIx: Refer to
.
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...