14
Dynamic Braking
14-2 | CFW700
F022 - Overvoltage
Dynamic braking actuation
Time
Time
Braking Resistor
Voltage (DB)
U
d
U
d
P0153
Rated U
d
DC Link Voltage (U
d
) (P0004)
Figure 14.1:
Dynamic Braking actuation curve
Steps to enable the dynamic braking:
Connect the braking resistor. Refer to item 3.2.3.2 - Dynamic Braking (standard built-in for sizes A, B, C and
D and optional built-in for size E - CFW700...DB...), of the user's manual.
Set P0151 at the maximum value: 400 V (P0296=0) or 800 V (P0296=1, 2, 3 or 4), according to the case, in
order to prevent the activation of the DC voltage regulation before the dynamic braking.