5
Programming Basic Instructions
5-6 | CFW700
5.6 INCOMPATIBILITY BETWEEN PARAMETERS
If any of the combinations listed below occur, the CFW700 goes to the “Config” state.
1. Two or more DIx (P0263...P0270) programmed for (8 = FWD/REV).
2. Two or more DIx (P0263 .... P0270) programmed for (9 = LOC/REM).
3. Two or more DIx (P0263 .... P0270) programmed for (14 = Ramp 2).
4. Two or more DIx (P0263 .... P0270) programmed for (15 = Speed/Torque).
5. Two or more DIx (P0263 .... P0270) programmed for (24 = Disable Flying Start).
6. Two or more DIx (P0263 .... P0270) programmed for (25 = DC Link Regulator).
7. Two or more DIx (P0263 .... P0270) programmed for (26 = Programming Off).
8. Two or more DIx (P0263 .... P0270) programmed for (27 = Load User 1).
9. Two or more DIx (P0263 .... P0270) programmed for (28 = Load User 2).
10. [P0202 programmed for (0=V/f 60 Hz) OR (1=V/f 50 Hz) OR (2=Adjustable V/f) OR (3=VVW)] AND [P0231=1
(No Ramp Ref.) OR P0231=2 (Max.Torque Cur) OR P0236=1 (No Ramp Ref.) OR P0236=2 (Max.Torque Cur)
OR P0241=1 (No Ramp Ref.) OR P0241=2 (Max.Torque Cur) OR P0246=1 (No Ramp Ref.) OR P0246=2 (Max.
Torque Cur)].
11. [P0202 programmed for (0=V/f 60 Hz) OR (1=V/f 50 Hz) OR (2=Adjustable V/f) OR (3=VVW)] AND [DIx (P0263...
P0270) programmed for (16=JOG+) OR (17=JOG-).
12. [P0224 programmed for (1=DIx) OR P0227 programmed for (1=DIx)] AND [without DIx (P0263...P0270)
programmed for (1=Run/Stop) AND without DIx (P0263...P0270) programmed for (2=General Enable) AND
without DIx (P0263...P0270) programmed for (3=Fast Stop).
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...