10
VVW Control
10-6 | CFW700
Step
Action/Result
Display indication
1
-
Monitoring Mode.
-
Press the
ENTER/MENU
key to get
into the first level of the programming
mode.
2
-
The
PARAM
group is selected, press
the
or
keys to select the
STARTUP
group.
3
-
Press
ENTER/MENU
when the
group is selected.
4
-
The parameter
“P0317 – Oriented
Start-up”
is then selected, press
the
ENTER/MENU
to get into the
parameter content.
5
-
Change the parameter P0317 to
“1 -
Yes”
, by using the
key.
6
-
Press
ENTER/MENU
to save.
7
-
In this moment the Oriented Start-up
routine is initiated and the
“CONF”
status is indicated at the keypad
(HMI).
-
The parameter
“P0000 - Access to
Parameters”
is selected. Change
the password to set the remaining
parameters if necessary.
-
Press the
key to the next
parameter.
8
-
If necessary, change
“P0296 - Line
Rated Voltage”
. This change will
affect P0151, P0153, P0185, P0321,
P0322, P0323 and P0400.
-
Press the
key to the next
parameter.
9
-
If necessary, change
“P0298 -
Applicat ion”
parameter. This
change will affect P0156, P0157,
P0158, P0401, P0404 and P0410
(this last one only if P0202 = 0, 1 or
2 - V/f modes). The time and level of
the IGBT overload protection will also
be affected.
-
Press the
key to the next
parameter.
Step
Action/Result
Display indication
10
-
Set parameter
“P0202 - Type
of Control”
pressing
“ENTER/
MENU”
. Press the
key to select
the desired option:
“[3]=VVW”
.
Then, press
“ENTER/MENU”
.
There are three options to exit the
oriented start-up:
1 - Running the Self-tunning;
2 - Manual settings of parameters
from P0409 to P0413;
3 - Changing P0202 from vector to
V/Hz control.
-
Press the
key to the next
parameter.
11
-
If necessary, change
“P0398 -
Motor Service Factor”
parameter.
This change will affect the current
and the time of the motor overload
protection operation.
-
Press the
key to the next
parameter.
12
-
If necessary, change
“P0399 - Motor
Rated Efficiency”
parameter.
-
Press the
key to the nex t
parameter.
13
-
If necessary, change
“P0400 -
Motor Rated Voltage”
parameter.
-
This change corrects the output
voltage by the factor “x = P0400/
P0296”.
-
Press the
key to the next
parameter.
14
-
If necessary, change
“P0401 -
Motor Rated Current”
parameter.
This change will affect P0156, P0157,
P0158 and P0410.
-
Press the
key to the next
parameter.
15
-
If necessary, change
“P0404 -
Motor Rated Power”
parameter.
This change will affect P0410.
-
Press the
key to the next
parameter.
16
-
If necessary, change
“P0403 - Motor
Rated Frequency”
parameter. This
change will affect P0402.
-
Press the
key to the next
parameter.
17
-
If necessary, change
“P0402 -
Motor Rated Speed”
. This change
will affect P0122 to P0131, P0133,
P0134, P0135, P0182, P0208, P0288
and P0289.
-
Press the
key to the next
parameter.
Figure 10.2:
VVW mode Oriented Start-up
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...