11
Vector Control
11-12 | CFW700
P0404 – Motor Rated Power
Adjustable
Range:
0 to 25 (refer to the next table)
Factory
Setting:
Motor
max-ND
Properties:
cfg
Access groups
via HMI:
MOTOR
Description:
Set it according to the used motor nameplate data.
Table 11.1:
P0404 (Motor Rated Power) setting
P0404
Motor Rated Power (hp)
0
0.33
1
0.50
2
0.75
3
1.0
4
1.5
5
2.0
6
3.0
7
4.0
8
5.0
9
5.5
10
6.0
11
7.5
12
10.0
13
12.5
14
15.0
15
20.0
16
25.0
17
30.0
18
40.0
19
50.0
20
60.0
21
75.0
22
100.0
23
125.0
24
150.0
25
175.0
NOTE!
When adjusted via keypad (HMI), this parameter may change the parameter P0329 automatically.
Refer to
item 12.5.2 - Vector Flying Start
.
P0405 – Encoder Pulse Number
Adjustable
Range:
100 to 9999 ppr
Factory
Setting:
1024 ppr
Properties:
cfg
Access groups
via HMI:
MOTOR
Description:
It sets the number of pulses per rotation (ppr) of the used incremental encoder.