Read only Parameters
16
CFW700 | 16-7
P0044 – kWh Output Energy
Adjustable
Range:
0 to 65535 kWh
Factory
Setting:
Properties:
ro
Access groups
via HMI:
READ
Description:
It indicates the energy consumed by the motor.
It indicates up to 65535 kWh, and then it gets back to zero.
By setting P0204=4, the value of the parameter P0044 is reset to zero.
This value is kept even when power is removed from the inverter.
NOTE!
The value indicated in this parameter is calculated indirectly, and must not be used to measure the
energy consumption.
P0045 – Enabled Fan Time
Adjustable
Range:
0 to 65535 h
Factory
Setting:
Properties:
ro
Access groups
via HMI:
READ
Description:
It indicates the total number of hours that the heatsink fan remained enabled.
It indicates up to 65535 hours, and then it gets back to zero.
By setting P0204=2, the value of the parameter P0045 is reset to zero.
This value is kept even when power is removed from the inverter.