Faults and Alarms
15
CFW700 | 15-7
Class 45
Class 40
Class 35
Class 30
Class 25
Class 20
Class 15
Class 10
Class 5
0
1
1x
0,1
1
100
10
1000
10000
100000
2x
3x
4x
5x
6x
7x
8x
9x 10x
2
3
4
5
6
7
9
10
8
Current x In for F.S. = 1.15
Current x In for F.S. = 1.00
Figure 15.3 (b):
Hot motor overload curves for loads of the HD and ND types
For the previous example, by plotting the 678 % value (x axis) of the Overload Current with the 4 seconds (y axis)
of the Overload Time in the graph of the
(hot motor), the thermal class to be selected will be the
class 15 (t15).
P0340 – Auto-Reset Time
Adjustable
Range:
0 to 255 s
Factory
Setting:
0 s
Properties:
Access groups
via HMI:
Description:
When a fault occurs (except F067 – Inverted Encoder/Motor Wiring and F099 – Invalid Current Offset), the
inverter can reset itself automatically after the time set in P0340 has elapsed.
NOTE!
The faults F051, F078 and F156 allow a conditional Reset, i.e., the Reset will only occur if the
temperature gets back to the normal operation range.
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...