![WEG CFW700 Programming And Troubleshooting Manual Download Page 150](http://html1.mh-extra.com/html/weg/cfw700/cfw700_programming-and-troubleshooting-manual_950676150.webp)
13
Digital and Analog Inputs and Outputs
13-20 | CFW700
(q) F > Fx
(2)
P0281 - P0282
Fx (P0281)
N
OFF
ON
Relay /
Transistor OFF
(r) No Alarm
Relay /
Transistor
ON
No Alarm
OFF
Time
Alarm
Figure 13.6 (q) and (r) (cont.):
Details on the operation of the digital and relay output functions
P0281 – Fx Frequency
Adjustable
Range:
0.0 to 300.0 Hz
Factory
Setting:
4.0 Hz
Properties:
Access groups
via HMI:
Description:
It is used in the digital output and relay functions:
F > Fx
(1)
and F > Fx
(2)
P0282 – Fx Hysteresis
Adjustable
Range:
0.0 to 15.0 Hz
Factory
Setting:
2.0 Hz
Properties:
Access groups
via HMI:
Description:
It is used in the digital output and relay functions:
F > Fx
(1)
and F > Fx
(2)
P0287 – Nx/Ny Hysteresis
Adjustable
Range:
0 to 900 rpm
Factory
Setting:
18 rpm
(15 rpm)
Properties:
Access groups
via HMI:
Description:
It is used in the
N > Nx
and
N < Ny
functions of the digital and relay outputs.
Summary of Contents for CFW700
Page 2: ......
Page 4: ......
Page 8: ...Summary...
Page 34: ...2 General Information 2 4 CFW700...
Page 38: ...3 About the CFW700 3 4 CFW700...
Page 56: ...7 Starting up and Settings 7 4 CFW700...
Page 58: ...8 Available Control Types 8 2 CFW700...
Page 78: ...10 VVW Control 10 8 CFW700...
Page 158: ...13 Digital and Analog Inputs and Outputs 13 28 CFW700...