2 Technical Description
2.6 Technical Data
Manual
36
SIPART DR21
C73000-B7476-C143-08
2.6.2
Standard controller
Power Supply
Rated voltage
230 V AC
115 V AC
24 V UC
g
switchable
Operating voltage range
195 to
264 V AC
97 to
132 V AC
20 to
28 V AC
20 to
35 V DC
1)
Frequency range
48 to 63 Hz
-- -- --
External current
I
Ext
2)
200 mA
Power consumption
Standard controller without options
without
I
Ext
active power/apparent
power (capacitive)
Standard controller with options
without
I
Ext
active power/apparent
power (capacitive)
Standard controller with options with
I
Ext
active power/apparent power
(capacitive)
5 W/9 VA
11 W/15 VA
15 W/19 VA
5 W/9 VA
11 W/15 VA
15 W/19 VA
4 W/6 VA
8.5 W/12 VA
12 W/17 VA
4 W
8.5 W
12 W
Permissible voltage breaks based on
0.85 U
N
and max. load
Time
3)
≤
20 ms
≤
20 ms
≤
20 ms
≤
20 ms
1)
including harmonic
2)
current transmitted from L+, DO, AO to external loads
3)
The load voltages of the AO are reduced hereby to 13 V, L+ to 15 V and the DO to 14 V
Table 2-1
Power supply standard controller
Analog inputs AI1 to AI2
Current
Rated signal range
0/4 to 20 mA
Modulation range
-0.1 to 22 mA
Input resistance
Difference (load)
248
Ω
±
1 %
Filter time constant
10 ms
Zero error
see AD-converter
Full scale error
see AD-converter
Linearity error
see AD-converter
Temperature influence
see AD-converter
Static destruction limit
±
40 mA
Parameterizable transmitter fault message
AI1/2
0 mA to 20 mA
4 mA to 20 mA
≤
-0.5 %;
≤
-2.5 %;
≥
106.25 %
≥
106.25 %
AI3/4
0/4 mA to 20 mA
≤
-2.5 %;
≥
106.25 %
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...