7 Application examples for configuring the controller
7.3 Configuration examples
Manual
202
SIPART DR21
C73000-B7476-C143-08
Configuration example
K3
Fixed setpoint controller as a K-controller
Controlled variable by a two-wire transmitter
x
w
I
y
Drive
The controlled variable x from the transmitter goes to the analog
input AI1 of the controller.
The transmitter is fed by the same lines. The input signal range
and the output manipulated variable of the controller are 4 to
20 mA.
Please read the foreword to chapter 7.1, page 193
Setting the structure switches:
S1 = 0
S2 = 0
S4 = 2, 3
S56 = 1
Slot 1
AI3
not
used
Slot 2
AI4
not
used
Slot 3
Limit value
Option module
6DR2801-8D
M1 A1
R2
M2
R1 A2
1
2
3
4
5
6
When using AI1 the feed voltage at the transmitter may
be only 15 V under worst case conditions.
--
I
+
x
--
I
+
AI1
--
PE
N
L
SIPART DR21 standard controller
PE
N
L
UC 24 C
AC 115 V
AC 230 V
6DR2100-5
(AC230 V/115 V)
6DR2100-4
(UC 24 C)
AI1
+
AI2
--
AI2
+
DI1 DI2 DO
1
DO
2
L+ AO
1
2
3
4
5
6
7
8
9
10
11
12
-
Δ
y
L
13
14
15
+
Δ
y
GND GND
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...