Functional description of the structure switches
3.10 Other functions of the standard controller
Manual
SIPART DR21
C73000-B7476-C143-08
119
Determine the respective physical value from the appropriate function tables for every U
n
or
graphically from the corresponding curve (interpolate if necessary) and enter the value for the
respective vertex value (L
-1
to L
11
) in physical variables in the structuring mode oFPA.
U
E
8 39.526
!
L8 900
7 35.124
!
L7 846
6 30.722
!
L6 790
5 26.32
!
L5 729
4 21.918
!
L4 664
3 17.516
!
L3 593
2 13.114
!
L2 514
1 8.712
!
L1 420
0 4.31
!
L0 300
-1 -0.092
!
L-1 0
t
A
t
E
U
E
=48.33 mV
60
50
40
30
20
10
0
0
100
200 300
400
500
600
700
800
900
1000 1200
110
100
90
80
70
60
50
40
30
20
10
0
-10
U
A
=4.31 mV
U
E
dA
dE
t [
˚
C]
%
n
Un [mV] vertex- t [
˚
C]
value
11 52.732
!
L11 1048
10 48,33
!
L10 1000
9
43.928
!
L9 951
[mV]
Figure 3-35 Example of linearization of a thermocouple type B Pt30Rh/Pt6, measuring range dA to dE
from 300 to 1000
C
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...