4 Installation
4.2 Electrical Connection
Manual
SIPART DR21
C73000-B7476-C143-08
137
-
Pin assignment for resistance potentiometer R S8 = 6, 7
2-Conductor terminal
3-Conductor terminal
Block diagram of UNI-module 6DR2800-8V
R
L4
R
p
R
L1
R
L4
R
p
R
L1
R
L2
1)
R
s
R
L4
≤
50
Ω
R
L1
+ R
L4
≤
50
Ω
1)
R
s
Shunt impedance only necessary if 2.8 k
Ω
< R
≤
5 k
Ω
R
S
⋅
R
p
R
S
+ R
p
≤
2,8 k, Rp > 5 K
Ω
not recommended
i
m
U
+REF
+
--
A
D
Sensor
6DR2800-8V
4
3
2
1
4
3
2
1
Figure 4-23 Connection UNI-module AI3 S8 = 6, 7
4.2.3.2 Connection examples for analog measuring inputs with the module
6DR2800-8J
In current inputs the input load resistance is between AI+ and AI--.
If the signal is still required during service work in which the terminal is disconnected, the input
load resistance must be connected to the terminal between AI+ and AI--. The internal 49.9
Ω
resistance must then be disconnected in 6DR2800-8J by appropriate rewiring.
AI+
AI -
20 mA
49.9
Ω
1 V/10 V
--
+
49.9
Ω
optionally
6DR2800-8J
AI+
AI -
20 mA
4
3
2
1
set 1 V jumper
Figure 4-24 Current input via options modules, internal or external 49.9
Ω
resistance
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...