7
Application examples for configuring the controller
7.3 Configuration examples
Manual
SIPART DR21
C73000-B7476-C143-08
211
Configuration example
L2
Manual control unit (HS) (
continued
)
The process variables controlled variable and manipulated variable can be dis-
played online on the HS. The setpoint can only be simulated as a flag, i.e. it must
be transmitted manually by the controller. For this, CB must be = 0 (S23 = 0) on the
HS. See also chapter 3.4.6, page 80 and figure 3-18, page 87.
AI1
--
PE
N
L
PE
N
L
UC 24 C
AC 115 V
AC 230 V
AI1
+
AI2
--
AI2
+
DI1 DI2
L+ AO
1
2
3
4
5
6
7
8
9
10 11
12
Slot 1
AI3
Slot 2
AI4
Slot 3
Limit value
1 2 3 4
5
6
1
2 3 4
Option module
6DR2800-8J
L
+
Δ
y
13 14 15
--
Δ
y
SIPART DR21 standard controller
6DR2100-5
(AC230 V/115 V)
6DR2100-4
(UC 24 C)
1 2
3 4
not
used
R +
not
used
--
I
+
x1
ly
yN
¡
©
¢
¦
§
¨
K-controller
Setting the structure switches of the K-controller:
S1 = 0, fixed setpoint controller
S2 = 0, K-controller
S15 = 4, X1
!
AI4
S18 = 1, yN
!
AI1
S61 = 1, Nw
!
DO1
S72 = 1
£
¥
¤
GND
GND GND
DO
1
DO
2
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...