5 Operation
5.4 Configuration modes
Manual
176
SIPART DR21
C73000-B7476-C143-08
D
CA/CE – fine adjustment (only if necessary)
Call parameter CA,
Set signal to start of scale
Correct the display with CA if necessary
Call parameter CE,
Set signal to full scale,
Correct the display with CE if necessary
5.4.6.4 Measuring range for thermocouple with external reference point (S8 = 2)
D
tb – external reference points-temperature
Set the external reference point temperature with tb. Specify temperature unit with S10.
Attention: tb has no effect at S9 = 10!
D
MA/ME – set measuring range
Call parameters MA, ME, set the start of scale and full scale according to the thermocouple
type (S9) and the temperature unit.
D
CA/CE – fine adjustment (only if necessary)
Call parameter CA,
Set signal to start of scale
Correct the display with CA if necessary
Call parameter CE,
Set signal to full scale,
Correct the display with CE if necessary
5.4.6.5 Measuring range for PT100 four-wire and three-wire connection
(S8 = 3,4)
D
MA/ME – set measuring range
Call parameters MA, ME, set range start and full scale:
Measuring range limits -200
_
C
≤
MA
≤
ME
≤
+850
_
C
Specify temperature unit with S10.
D
CA/CE – fine adjustment (only if necessary)
Call parameter CA,
Set signal to start of scale
Correct the display with CA if necessary
Call parameter CE,
Set signal to full scale,
Correct the display with CE if necessary
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...