7 Application examples for configuring the controller
7.4 Configuring tool, forms
Manual
218
SIPART DR21
C73000-B7476-C143-08
Settings SIPART DR21, controller number / measuring point . . . . . . . . . . . . . . . . . .
Parameter
onPA
Digital indication on display
Fac-
t
Dimen-
i
3 (w/x) for preset
tory
setting
sion
Parameter meaning
9 (y)
setting
Filter time constant xd (adaptive)
tF
1.000
s
(
p
)
Derivative action gain
vv
5.000
1
g
Proportional gain factor
cP
0.100
1
p
g
Integral-action time
tn
9984
s
g
Derivative-action time
tv
oFF
s
Response threshold
AH
0.0
%
p
Operating point
YO
Auto
%
Output variable limiting start
YA
--5.0
%
p
g
Output variable limit end (YA
≤
YE)
YE
105.0
%
p
(
)
y actuating time open/period heating
tP
1.000
s
y
g
p
p
g
y actuating time open/period cooling
tM
1.000
s
min. actuating pulse pause
tA
200
ms
g p
p
min. actuating pulse length
tE
200
ms
Filter time constant AI1
t1
1.000
s
Filter time constant AI2
t2
1.000
s
Filter time constant AI3
t3
1.000
s
Filter time constant AI4
t4
1.000
s
Multiplicative constant
c1
0.000
1
p
Multiplicative constant
c2
0.000
1
p
Additive constant
c3
0.000
100 %
Multiplicative constant
c4
1.000
1
p
Additive constant
c5
0.000
100 %
Multiplicative constant
c6
0.0
1
p
Multiplicative constant
c7
1.000
1
Display refresh rate
dr
1.000
s
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...