7
Application examples for configuring the controller
7.3 Configuration examples
Manual
SIPART DR21
C73000-B7476-C143-08
207
Configuration example
Z1
Fixed setpoint control with PD two-position controller
The controlled variable comes from a thermocouple with internal refer-
ence point.
The controlled variable of the thermocouple is fed directly to the analog input
AI3. The type of thermocouple is selected with S9. The measuring range must
be set in the CAE menu (see chapter5.4.5, page 165).
System adaptation with the parameters Y1 and Y2.
Two-position controller structure see chapter 3.6, page 94
w
+y / --y
AI1
--
PE
N
L
PE
N
L
UC 24 C
AC 115 V
AC 230 V
AI1
+
AI2
--
AI2
+
DI1 DI2 DO
1
DO
2
L+ AO
1
2
3
4
5
6
7
8
9
10
11
12
Setting the structure switches:
S2 = 1
S6 = 4 to 7
S8 = 1
Slot 1
AI3
Slot 2
AI4
Slot 3
Limit value
Option module
6DR2801-8D
M1 A1
R2
M2
R1 A2
1
2
3
4
5
6
not
used
1
2
3
4
Option module
6DR2801-8V
L
+
Δ
y
13
14
15
--
Δ
y
S15 = 3
S27 = 8
S54 = 3
Please note the possibilities of setting the operating point in the P-controller (page 93) and the foreword in
chapter 7.1, page 193
SIPART DR21 standard controller
6DR2100-5
(AC230 V/115 V)
6DR2100-4
(UC 24 C)
L
1
2
3
4
R
L
R
comp
Cooling
Heating
N
--
+
Σ
R
L
≤
300
Ω
--
+
I
GND GND
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...