3
Functional description of the structure switches
3.4 Controller types (S1, S42 to S45)
Manual
SIPART DR21
C73000-B7476-C143-08
79
The ratio factor v (at xd = 0) is determined partly by the transmission factors K of the
transmitters (measuring ranges).
x
1
= Q
G
⋅
K
G
with the values from the example
100 %
3000 m
3
/h
K
G
=
x
2
= Q
L
⋅
K
L
100 %
12,000 m
3
/h
K
L
=
v =
= Q
G
Q
L
x
1
x
2
⋅
with
Q
G
Q
L
1
L
⋅
λ
=
v =
1
L
⋅
λ
K
G
K
L
K
G
K
L
⋅
With the values from the example
v = 1
λ
⋅
1
4
100 %
⋅
h
⋅
12,000 m
3
3,000 m
3
⋅
100 %
⋅
h
⋅
the result is
v =
1
λ
i.e. the choice of the transmitter ranges has been made so
that
K
G
K
L
=
1
L
corresponds to
The desired adjustment range of
λ
gives:
vA =
=
1
λ
E
1
1,25 = 0,8
vE =
=
1
λ
A
1
0,75 = 1,333
vA and vE are set in the structuring mode oFPA. By setting the nominal ratio wv from 0 to 1
the ratio factor v can now be adjusted from 0.8 to 1.33 or the air factor
λ
from 1.25 to 0.75.
0.75
1.2
1.25
0.8
0.9
1
1.1
1.2
0.2
0.6
1.33
1.3
1
0.8
0.4
0
0.8
1.1
0.9
1
wv
v
λ
Figure 3-14 Relationship ratio factor v and air factor
λ
to standardized nominal ratio wv
If the combustion is also to take place at small flow volumes with excess air, the constant c
must be set negative. Figure 3-14 shows the gas-/air ratio in the controlled state at different
air factors
λ
and c = 0 as well as at
λ
= 1 and c
<
0, i.e. with excess air.
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...