5 Operation
5.4 Configuration modes
Manual
164
SIPART DR21
C73000-B7476-C143-08
oFPA
Offline parameter list
y display
w / x display
Parameter
Param-
names
Min.
Max.
Factory
setting
Unit
Decimal point w/x num.
dP
_.------
--------
_ _ _.--
--
Start of scale
dA
--1999
9999
0.0
Full scale
dE
--1999
9999
100.0
Alarm 1
A1
--110% to 110%
5.0
Alarm 2 (A2
≤
A1)
A2
from dA, dE
--5.0
Alarm 3
A3
at S76 / S77 =
5.0
Alarm 4 (A4
≤
A3)
A4
0 to 5 and 17
--5.0
Hysteresis alarms
HA
0.1
10.0
1.0
%
Setpoint start
SA
--10% to 110%
--5.0
Setpoint end
SE
from dA, dE
105.0
Safety setpoint
SH
0.0
Setpoint ramp time
tS
oFF/0.100
9984
oFF
min
Ratio factor start
vA
0.000
9.999
0.000
1
Ratio factor end
vE
0.000
9.999
1.000
1
Safety output variable
YS
--10.0
110.0
0.0
%
Split range left (Y1
≤
Y2)
Y1
0.0
100.0
50.0
%
Split range right
Y2
0.0
100.0
50.0
%
L--1
--10.0
110.0
--10.0
% (1)
L0
--10.0
110.0
0.0
% (1)
L1
--10.0
110.0
10.0
% (1)
O t t
l
f th li
i
L2
--10.0
110.0
20.0
% (1)
Output values of the linearizer
L--1 (--10%) to L11 (110%) are
L3
--10.0
110.0
30.0
% (1)
L--1 (--10%) to L11 (110%) are
equidistant input vertex points
L4
--10.0
110.0
40.0
% (1)
equidistant input vertex points
(1) Note
L5
--10.0
110.0
50.0
% (1)
(1) Note
At S21 5 values standardized to
L6
--10.0
110.0
60.0
% (1)
At S21=5, values standardized to
dA to dE.
L7
--10.0
110.0
70.0
% (1)
dA to dE.
L8
--10.0
110.0
80.0
% (1)
L9
--10.0
110.0
90.0
% (1)
L10
--10.0
110.0
100.0
% (1)
L11
--10.0
110.0
110.0
% (1)
Decimal point
1)
Pd
_.------
_ _ _ _
_ _ _.--
Start value
1)
Ad
--1999
9999
0.0
--
Full scale value
1)
Ed
--1999
9999
100.0
1)
as of software version -A9, only in ratio controller (S1 = 3)
Display range of controlled variable x1 and the weighted commanding process variable w (S81 = 7)
Table 5-4
Offline parameter list
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...