Application examples for configuring the controller
7.2 Working with different setpoints
Manual
SIPART DR21
C73000-B7476-C143-08
197
Example 3
Four-setpoint operation with one slave controller with Internal/
External switching and CB signal through the digital input
The analog input AI2/w
E
is overcontrolled to 0 or 100%:
wi
setpoint which can be adjusted on the front
w
E
setpoint limit fixed by parameterization oFPA (setpoint limit start SA), w
E
over
controlled to 0 %.
SH
safety setpoint set by parameterization.
w
E
setpoint limit fixed by parameterization oFPA (setpoint limit end SE)
w
E
overcontrolled to 100 %.
Switchings take place:
wi=
key (16) to Internal
w
E
= key (16) to External (INT), CB signal High (CB). AI2 overcontrolled to 0% (SA)
SH= key (16) to External, CB from High to Low (CB)
w
E
= key (16) to External (INT), CB signal High (CB). AI2 overcontrolled to 100% (SE)
Restriction of this circuit wi and SH must be within the limits SA to SE.
Also only the active setpoint can be displayed at S81 = 2/3. SH can only be reached by the
transition INT
∧
CB to INT
∧
CB.
w
i
w
E
(SA)
SH
w
E
(SE)
t
0
w (%)
100
S1 = 1
wE on AI2
S17 = 2
CB on DI1
S23 = 1
S42 = 2
S43 = 0
S44 = 1
S45 = 1
Int/Ext key
100 %
DI1
AI2
Int
Int
CB
CB
0 %
Attention!
SH (safety setpoint) can only
be selected based on w
E
(ex-
ternal setpoint).
Figure 7-3 Setpoint curve according to example 3
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...