5 Operation
5.4 Configuration modes
Manual
174
SIPART DR21
C73000-B7476-C143-08
D
Calling, setting and leaving the CAE3 menu
- Press the shift key (6) for about 5 s until ”PS” flashes in the y display (9).
- Select the CAE3 menu with the
Δ
w keys (14), (15)
- To enter the CAE3 menu, press the Enter key (11) for about 3 s.
- Select the CAE3 parameters with the
Δ
y keys (7), (8)
- Set the CAE3 parameters with the
Δ
w keys (14), (15)
- You return to the process operation mode by pressing the Exit key (16) twice.
D
The following parameters are available in the CAE3 menu for setting the measuring
range and adjustment
y display
parameter
name
w/x display
setting range
Factory
setting
Display
unit
Meaning/function of
parameter
Display and
function only
at:
tb
1)
0 to 400.0
50
_
C,
_
F, K
Reference temperature
external reference point
S8 = 2
Mr
0.00 to 99.99
10
Ω
M
easuring of
R
Ln.
(Pt100-2L)
S8 = 5
Cr
Difference value to Mr
Ω
C
alibr. of
R
Ln. (Pt100-2L)
S8 5
MP
_.------ to ____
physical
Dimension
Decimal point measuring
range
MA
2)
--19999 to 9999
0.0
Dimension
depending
M
easuring range
s
tart
ME
2)
--19999 to 9999
100.0
depending
on the
M
easuring range
f
ull scale
S8 = 0 to 7
CA
act. measured value
±
Δ
A
3)
measuring
variable
C
alibr. Meas. range
S
tart
CE
act. measured value
±
Δ
E
3)
variable
4)
C
alibr. Meas. range
f
ull
scale
PC
5)
no, YES, no C
no C
--
P
reset
C
alibration
S8 = 0 to 5
Table 5-7
CAE3-menu parameter list
1)
If no specified thermocouple type is selected with S9 = 10, the parameter tb has no effect.
2)
The set measuring range is transferred as a standardized number range from 0 to 1 to the controller.
If the measured value mode is to be displayed physically, the offline parameters
dP, dA and dE must be set accordingly.
3)
For S8 = 0 to 5 :
Δ
A,
Δ
E do not appear as own parameters. The correction values for calibrating the start or full scale
of the measuring range are arbitrary.
4)
For S8 = 6, 7 the unit of the CA/CE display is in %.
5)
For S8 = 0 to 5 : With
Δ
A =
Δ
E = 0, PC = no C is displayed, it is not possible to switch over with the
Δ
w--keys (7), (8)
to PC = YES. By adjusting CA/CE, PC = no is displayed, switching to PC = YES is possible. If PC = YES is displayed
Δ
A =
Δ
E = 0 can be set with the Enter key (press for approx. 3 s), whereupon PC = no C is displayed.
The corresponding settings of the CAE3 menu for the different signal transmitters are described
below.
The range and thus the current measured value can be corrected with the parameters CA/CE to
compensate tolerances of the transmitters or adjustments with other display instruments (for
S 8 = 0 to 5).
To avoid measuring errors, the assembly instructions in chapter 4.2.2, page 130 and especially
the maximum permissible line resistances (see table 2-3, page 41) must be observed in the de-
termination of the measuring range.
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...