7 Application examples for configuring the controller
7.3 Configuration examples
Manual
206
SIPART DR21
C73000-B7476-C143-08
Configuration example
S3
Ratio control, S-controller (internal feedback)
Commanded process variable and commanding variable directly from
two-wire transmitters
The commanded process variable x1 from the transmitter goes to the analog
input AI1, the commanding process variable is connected to the analog input AI2.
The input signal ranges are 4 to 20 mA. The feedback of the final control element
position comes from a resistance potentiometer to the analog input AI4.
The setting of the ratio factor range is described in chapter 3.4.5, page 75.
x
2
w
y
Drive
y
R
x
1
AI1
--
PE
N
L
PE
N
L
UC 24 C
AC 115 V
AC 230 V
AI1
+
AI2
--
AI2
+
DI1 DI2 DO
1
DO
2
L+ AO
1
2
3
4
5
6
7
8
9
10
11
12
Setting the structure switches:
S1 = 3
S2 = 2
S4 = 2, 3
S5 = 2, 3
Slot 1
AI3
Slot 2
AI4
Spark quench-
ing internal
Slot 3
Limit value
Option module
6DR2801-8D
M1 A1
R2
M2
R1 A2
1
2
3
4
5
6
not
used
M/A
S
E
1
2
3
4
Option module
6DR2800-8R
L
+
Δ
y
13
14
15
--
Δ
y
S7 = 0, 1
S19 = 4
S54 = 1
Please read the foreword in chapter 7.1, pg. 193 and the warnings in chapter 2.1 (from page 17)
SIPART DR21 standard controller
6DR2100-5
(AC230 V/115 V)
6DR2100-4
(UC 24 C)
R = R
A
+
Δ
R + R
E
L
R
C
N
Perform spark
quenching according
to EMC requirements!
R
C
I
+
--
R
A
R
E
S
I
+
--
x
2
x
1
When using the analog inputs AI1 and AI2 the
feed voltage at the transmitter may be only 15 V
under worst case conditions.
1
2
3
4
GND
GND GND
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...