5 Operation
5.4 Configuration modes
Manual
162
SIPART DR21
C73000-B7476-C143-08
D
Error messages of the adaptation procedure
yBL
direction-dependent blocking mode via the control signals
⇒
n.ddc
tracking or DCC mode by control signals
⇒
ovEr
>
10 % overshoot of the transient function
Shot
⇒
adaptation of sufficient quality is possible
FASt
because of too small a line time constant no
adaptation of sufficient quality is possible
P.oFL
x outside the measuring span 0 to 100 %
⇒
n.End
at 67 % tU full scale value not reached yet
⇒
tU selected too small
⇒
loop cannot reach full scale value,
e.g. integrally active line
⇒
transient recovery time t
95
>
12 h
SMAL
x after 50 % tU still within starting band
⇒
tU selected too small
⇒
y step too small
PASS
step response in wrong direction within
30 % tU
⇒
Change controller direction of effect (S46)
⇒
control loop undershoot (all pass loop),
all-pass loops not defined among
loop models
y.OFL
y outside the manipulated variable limits Y
A
, Y
E
⇒
(see online parameters)
nody
after expiry of the step command the y step
in the S- controller is not yet executed correctly
⇒
Error messages Explanation
digital
x/w display
y
Manual
y too big or too small
Check position feedback and drive of the final
control element
y
Manual
y too big or too small
(transient recovery time t
95
< 5 s)
cancel mode of
operation
-10 0
y
% tU
StAt
not stable at 10 % tU after
Start of adaptation
⇒
wait and restart adaptation
-10 0
y
% tU
30
100
x, y
x, y
100
-10 0
y
% tU
50
100
x, y
-10 0
y
% tU
67
100
x, y
-10 0
y
% tU
67
100
x, y
Si
safety operation via the control signals
⇒
Table 5-3
Adaptation error messages
Summary of Contents for SIPART DR21
Page 1: ...SIPART DR21 C73000 B7476 C143 08 1 SIPART DR21 6DR 210 Edition 08 2010 Manual ...
Page 2: ...SIPART DR21 C73000 B7476 C143 08 2 ...
Page 148: ...4 Installation 4 2 Electrical Connection Manual 148 SIPART DR21 C73000 B7476 C143 08 ...
Page 180: ...5 Operation 5 5 CPU self diagnostics Manual 180 SIPART DR21 C73000 B7476 C143 08 ...
Page 242: ...Manual 242 SIPART DR21 C73000 B7476 C143 07 ...