Functions, monitoring and protective functions
9.3 Drive functions
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
511
WARNING
Unexpected motor movement during motor identification in the rotating mode
When selecting motor identification with optimization in the rotating mode, after
commissioning, the drive initiates that the motor rotates with speeds that can reach the
maximum motor speed.
•
Observe the general safety instructions.
•
Ensure that the EMERGENCY STOP functions are fully functional when commissioning
the drive.
Note
Speed controller optimization for operation with encoder
If speed controller optimization is carried out for operation with an encoder, the control mode
will be temporarily changed over to encoderless speed control automatically, in order to be
able to carry out the encoder test.
9.3.1.3
Shortened rotating measurement
A normal rotating measurement cannot always be performed when the load is connected.
When switching on the motor for the first time, a moment of inertia measurement and the
measurement of the magnetization current and the saturation characteristic can be
performed with a simplified measuring procedure. The following settings apply for the
shortened rotating measurement:
●
Measurement shortened (p1959.12 = 1)
●
After measurement: Direct transfer to operation (p1959.13 = 1)
During the shortened rotating measurement, the drive is not controlled up to the rated speed
but up to the value set in p1965 (factory setting, 40%). Parameter p1961 can be adjusted at
the plant, but it must be high enough to ensure that the machine has left open-loop
controlled operation. The machine should be operated in no-load operation (torque < 30% of
M
rated
) as far as is possible.
During the shortened rotating measurement the saving of parameters is disabled, because
parameter adjustments are automatically made for the measurement, which are to be
reassigned after the measurement.
Shortened measurement (p1959.12 = 1)
If p1959.12 = 1 is set, a shortened rotating measurement is carried out. In this case, the
magnetizing current and moment of inertia are determined with a somewhat lower degree of
accuracy; the vibration test is no longer required.
After the end of the measurement, the drive is moved to standstill and all the parameters
modified for performing the measurement are set to their original values.
Summary of Contents for SINAMICS S150 NEMA
Page 1: ......
Page 2: ......
Page 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Page 861: ......
Page 862: ......