Technical specifications
12.3 Technical specifications
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
823
Article no.
6SL3710- 7LG38-1AU3
7LG38-8AU3
7LG41-0AU3
Fuse type per phase
7)
Rated current
Frame size acc. to IEC 60269
UL file no. E167357
A
3NE1334-2
2 x 500
2
3NE1334-2
2 x 500
2
3NE1436-2
2 x 630
3
SCCR (short circuit current rating)
according to UL508A File no.
E83449
8)
na
65
65
65
SCCR (short circuit current rating)
according to UL508A File no.
E83449, with option L27 (higher
SCCR value)
kA
84
100
100
Minimum short-circuit current
9)
A
2000
2000
2500
1)
Rated output of a typical 6-pole standard induction motor based on I
L
or I
H
at 3-ph. 500 V AC 50 Hz or 3-ph. 690 V AC
50 Hz.
2)
Shaft output of the matching motor based on the current according to NEC table 430-250.
3)
The currents are based on a line power factor of cos
φ
= 1.
4)
The base-load current I
L
is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
5)
The base-load current I
H
is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
(see "Overload capability").
6)
The current values given here are based on the rated output current.
7)
The SCCR value of the enclosed drive is based on the fuses listed. Substitutes are not permitted.
8)
In conjunction with the specified fuses or circuit breakers.
9)
Minimum current required for reliably triggering protective devices.