Electrical installation
4.8 Signal connections
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
109
X530: 4 digital inputs
Table 4- 21 Terminal block X530
Connector Terminal
Designation
1)
Technical specifications
1
DI 4
Voltage: - 3 … +30 V
Current consumption typical: 10 mA at 24 V DC
Input delay:
For "0" to "1": typ. 50 µs, max. 100 µs
For "1" to "0": typ. 130 µs, max. 150 µs
Electrical isolation:
Reference potential is terminal M2
Signal level (including ripple)
High level: 15 … 30 V
Low-level: -3 … +5 V
2
DI 5
3
DI 6
4
DI 7
5
M2
6
M
Max. connectable cross-section:
- Standard version: #16 AWG (1.5 mm²)
- Version with option G65: #14 AWG (2.5 mm²)
1)
DI: digital input; M2: ground reference; M: electronics ground
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must be connected.
This is achieved through one of the following measures:
1.
Provision of the ground reference of the digital inputs.
2.
A jumper to terminal M. (Note: This removes the electrical isolation for these digital
inputs.)
Summary of Contents for SINAMICS S150 NEMA
Page 1: ......
Page 2: ......
Page 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Page 861: ......
Page 862: ......