Operation
6.11 Communication via EtherNet/IP
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
413
Table 6- 54 Class Attribute
No. Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Parameter access to drive object 0 (DO 0) is realized via this class.
Example: Read parameter 2050[10] (connector output to interconnect the PZD received from
the fieldbus controller)
Get Attribute single function with the following values:
●
Class = 401 hex
●
Instance = 2050 = 802 hex
≙
parameter number
●
Attribute = 10 = A hex
≙
Index 10
Example: Parameter 1520[0] writing (upper torque limit)
Set Attribute single function with the following values:
●
Class = 401 hex
●
Instance = 1520 = 5F0 hex
≙
parameter number
●
Attribute = 0 = 0 hex
≙
index 0
●
Data = 500.0 (value)
Parameter Object, Instance Number: 401 hex ... 43E hex
Supported services
Class
•
Get Attribute all
•
Get Attribute single
Instance
•
Get Attribute all
•
Set Attribute single
Table 6- 55 Class Attribute
No. Service
Type
Name
1
get
UINT16
-
2
get
UINT16
Max slot num
3
get
UINT16
Max slot ID
Parameter access to drive object 0 (DO 0) is realized via this class.
The class structure is analog to 401 hex. Drive object (DO) is selected via the class number.
Example:
0x401 -> DO 1
0x402 -> DO 2
...
0x43E -> DO 62