Operation
6.9 Communication via PROFINET IO
Enclosed Drives
380
Operating Instructions, 12/2018, A5E36652151A
6.9.6
PROFIenergy
6.9.6.1
Description
PROFIenergy is an energy management system for production plants, based on the
PROFINET communication protocol. The functionality is certified in the PROFIenergy profile
of the PNO. Drive units which have PROFIenergy functionality, can be certified in an
approved laboratory. Certified devices support the PROFIenergy commands and respond
accordingly to the requirements and operating states.
SINAMICS supports the PROFIenergy profile V1.1. PROFIenergy commands are acyclically
transferred from the controller to the drive with PROFINET data sets. The PROFIenergy
commands are transferred using the PROFINET data set 0x80A0.
PROFIenergy data set access is only accepted via connection type "RT connection" or
"IRT connection".
If access is made via another type of connection (e.g. a supervisor connection, system
redundancy connection), accessing the data set is rejected with error code 0x80B0 "Invalid
Index".
There is exactly one PROFIenergy access point (PESAP) and this is on the MAP submodule
of the CU drive object.
If access is made via another module/submodule, the data set access is rejected with error
code 0x80B0 "Invalid Index".
PROFIenergy properties of the SINAMICS drive system
SINAMICS drive system devices meet the following requirements:
●
Certified for PROFIenergy
●
PROFIenergy function unit Class 3
●
PROFIenergy energy-saving mode 2