Commissioning
5.7 Commissioning an encoder with gear factor
Enclosed Drives
260
Operating Instructions, 12/2018, A5E36652151A
Digital outputs
●
The "enable pulses" signal is output at digital output 0 (X542:2 and 3).
●
The “no fault active” signal is output at digital output 1 (X542:5 and 6) (protection against
wire breakage).
●
The "ready for power up" signal is output at digital output 8 (X541:2).
5.7
Commissioning an encoder with gear factor
Description
When encoders are commissioned (p0010 = 4), a gearbox must be parameterized by means
of parameters p0432 (numerator), p0433 (denominator), and p0410 (sign).
To ensure that the commutation position can be accurately determined from the encoder
angle, the following applies:
•
For resolvers:
z
p
= number of poles
•
For all other absolute
encoders:
z
p
= number of poles
•
Where n is the gear factor:
The encoder commissioning program ensures that this uniqueness condition is observed
and, if necessary, prevents the system from exiting the commissioning program or outputs
an error message.
Sign bit p0410 inverts the calculated encoder angle and the speed, thereby yielding a
negative gear factor.