Functions, monitoring and protective functions
9.4 Extended functions
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
627
Commissioning
The "extended monitoring functions" function module can be activated by running the
commissioning wizard. Parameter r0108.17 indicates whether it has been activated.
Function diagrams
FD 8010
Speed messages 1
FP 8011
Speed messages 2
FD 8013
Load monitoring
Parameters
•
p2150
Hysteresis speed 3
•
p2151
CI: Speed setpoint for messages
•
p2161
Speed threshold 3
•
p2181
Load monitoring, response
•
p2182
Load monitoring, speed threshold 1
•
p2183
Load monitoring, speed threshold 2
•
p2184
Load monitoring, speed threshold 3
•
p2185
Load monitoring, speed threshold 1 upper
•
...
•
p2190
Load monitoring, speed threshold 3 lower
•
p2192
Load monitoring, delay time
•
r2198.4 |n_set|
≤
p2161
•
r2198.5 n_set > 0
•
r2198.11 Load monitoring displays alarm
•
r2198.12 Load monitoring displays fault