Operation
6.11 Communication via EtherNet/IP
Enclosed Drives
410
Operating Instructions, 12/2018, A5E36652151A
TCP/IP Interface Object, Instance Number: F5 hex
Supported services
Class
•
Get Attribute all
•
Get Attribute single
Instance
•
Get Attribute all
•
Get Attribute single
•
Set Attribute single
Table 6- 50 Class Attribute
No. Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Table 6- 51 Instance Attribute
No. Service
Type
Name
Value/explanation
1
get
UNIT32 Status
Fixed value: 1 hex
1: Configuration acknowledged, by DHCP or
saved values
2
get
UNIT32 Configuration
Capability
Fixed value: 94 hex
4 hex: DHCP supported,
10 hex: Configuration can be adjusted,
80 hex: ACD-capable
3
get, set UNIT32 Configuration
Control
1 hex: Saved values
3 hex: DHCP
4
get, set UNIT16
Physical link
Path Size (in WORDs)
Fixed value: 2 hex
UNIT8
Path
20 hex,
F6 hex,
24 hex,
05 hex, where 5 hex is the number of instances of
F6 hex (four physical ports plus one internal port).
5
get, set STRING Interface
Configuration
r61000: Name of station
UNIT32
r61001: IP address
6
get, set UNIT16 Host Name
Host Name Length
STRING
-
10
get, set
UNIT8
Select ACD
local OM flash:
0: Disabled,
1: Enabled
11
get, set
UNIT8
Last Conflict
Detected
local OM flash ACD Activity
UNIT8
local OM flash Remote MAC
UNIT8
local OM flash ARP PDU