Operation
6.13 Communication services and used port numbers
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
431
6.13
Communication services and used port numbers
The drive device supports the protocols listed in the following table. The address
parameters, the relevant communication layer as well as the communication role and the
communication direction are specified for each protocol.
This information allows you to match the security measures for the protection of the
automation system to the used protocols (e.g. firewall). As the security measures are limited
to Ethernet and PROFINET networks, no PROFIBUS protocols are listed in the table.
The following table shows the various layers and protocols that are used.
Layers and protocols
Report
Port number
(2) Link layer
(4) Transport layer
Function
Description
PROFINET protocols
DCP
Discovery and
configuration
protocol
Not relevant
(2) Ethernet II and
IEEE 802.1Q and
Ethertype 0x8892
(PROFINET)
Accessible
nodes,
PROFINET
Discovery and
configuration
DCP is used by PROFINET to determine
PROFINET devices and to make basic
settings.
DCP uses the special multicast MAC
address:
xx-xx-xx-01-0E-CF,
xx-xx-xx = Organizationally Unique
Identifier
LLDP
Link Layer
Discovery
protocol
Not relevant
(2) Ethernet II and
IEEE 802.1Q and
Ethertype 0x88CC
(PROFINET)
PROFINET
Link Layer
Discovery
protocol
LLDP is used by PROFINET to determine
and manage neighborhood relationships
between PROFINET devices.
LLDP uses the special multicast MAC
address:
01-80-C2-00-00-0E
MRP
Media
Redundancy
Protocol
Not relevant
(2) Ethernet II and
IEEE 802.1Q and
Ethertype 0x88E3
(PROFINET)
PROFINET
medium
redundancy
MRP enables the control of redundant
routes through a ring topology.
MRP uses the special multicast MAC
address:
xx-xx-xx-01-15-4E,
xx-xx-xx = Organizationally Unique
Identifier
PTCP
Precision
Transparent
Clock Protocol
Not relevant
(2) Ethernet II and
IEEE 802.1Q and
Ethertype 0x8892
(PROFINET)
PROFINET
send clock and
time synchroni-
zation, based
on IEEE 1588
PTC allows a time delay measurements to
be made between RJ45 ports – therefore
send cycle synchronization and time
synchronization.
PTCP uses the special multicast MAC
address:
xx-xx-xx-01-0E-CF,
xx-xx-xx = Organizationally Unique
Identifier
Summary of Contents for SINAMICS S150 NEMA
Page 1: ......
Page 2: ......
Page 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Page 861: ......
Page 862: ......