Functions, monitoring and protective functions
9.3 Drive functions
Enclosed Drives
598
Operating Instructions, 12/2018, A5E36652151A
9.3.25.13
Troubleshooting, causes and remedies
Table 9- 9
Fault profiles, possible causes and remedies
Fault profile
Fault description
Remedy
No fault
–
F3x101 (zero mark
failed)
Check that the connection
assignment is correct
(A interchanged with -A or
B interchanged with -B)
F3x100 (Zero mark
distance error)
Check whether the
connection assignment is
correct (R interchanged
with -R)
Interjected zero mark
Use zero mark tolerance