Operation
6.5 Setpoint sources
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
289
Signal flow diagram
Figure 6-14 Signal flow diagram: Motorized potentiometer
Function diagram
FD 3020
Motorized potentiometer
Parameters
•
p1030
Motorized potentiometer, configuration
•
p1037
Motorized potentiometer, maximum speed
•
p1038
Motorized potentiometer, minimum speed
•
p1047
Motorized potentiometer, ramp-up time
•
p1048
Motorized potentiometer, ramp-down time
•
r1050
Motorized potentiometer, setpoint after the ramp-function generator
6.5.3
Fixed speed setpoints
Description
A total of 15 variable fixed speed setpoints are available.
The default setting specified for the setpoint sources during commissioning via STARTER or
the operating panel makes three fixed speed setpoints available. They can be selected via
terminals or fieldbus.