Operation
6.14 Parallel operation of communication interfaces
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
435
Note
Parallel operation of PROFIBUS and PROFINET
Either the isochronous mode or PROFIsafe functionality can be assigned to an interface via
p8815 (IF1 or IF2).
Example:
•
p8815[0] = 1: IF1 supports the isochronous mode.
•
p8815[1] = 2: IF2 supports PROFIsafe.
Additional configuration options are available if additionally the PROFINET module CBE20 is
inserted in the CU320-2 DP:
•
p8839[0] = 1 and p8839[1] = 2: PROFIBUS isochronous, PROFINET cyclic
•
p8839[0] = 2 and p8839[1] = 1: PROFINET isochronous, PROFIBUS cyclic
Parameters for IF2
The following parameters are available in order to optimize the IF2 for a PROFIBUS or
PROFINET interface:
●
Receive and send process data:
r8850, p8851, r8853, r8860, p8861, r8863
1)
●
Diagnostic parameters:
r8874, r8875, r8876
1)
●
Binector-connector converters:
p8880, p8881, p8882, p8883, p8884, r8889
1)
●
Connector-binector converters:
r8894, r8895, p8898, p8899
1)
1)
Significance of 88xx identical to 20xx
Note
Using the HW Config configuration tool, a PROFIBUS slave / PROFINET device with two
interfaces cannot be shown. In parallel operation, this is the reason that SINAMICS drive
appears twice in the project or in 2 projects, although physically it is just one device.
Parameters
p8839
PZD interface hardware assignment
Description:
Assigning the hardware for cyclic communication via PZD interface 1 and interface 2.
Value:
0: Inactive
1: Control Unit onboard
2: COMM BOARD
99: Automatic
Summary of Contents for SINAMICS S150 NEMA
Page 1: ......
Page 2: ......
Page 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Page 861: ......