Electrical installation
4.9 Additional connections
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
123
Table 4- 32 Max. pulse frequency when a dv/dt filter plus Voltage Peak Limiter is used in units with a rated pulse
frequency of 1.25 kHz
Article no.
6SL3710-...
Unit rating
[HP / kW]
Output current for a pulse
frequency of 1.25 kHz [A]
Max. pulse frequency when a dv/dt filter
plus Voltage Peak Limiter is used
Supply voltage 3-phase 380 ... 480 V AC
7LE36-1AU3
500 / 315
605
2.5 kHz
7LE37-5AU3
600 / 400
745
2.5 kHz
7LE38-4AU3
700 / 450
840
2.5 kHz
7LE41-0AU3
800 / 560
985
2.5 kHz
7LE41-2AU3
1000 / 710
1260
2.5 kHz
7LE41-4AU3
1000 / 800
1405
2.5 kHz
Supply voltage 3-phase 500 ... 690 V AC
7LG28-5AU3
75 / 75
85
2.5 kHz
7LG31-0AU3
75 / 90
100
2.5 kHz
7LG31-2AU3
100 / 110
120
2.5 kHz
7LG31-5AU3
150 / 132
150
2.5 kHz
7LG31-8AU3
150 / 160
175
2.5 kHz
7LG32-2AU3
200 / 200
215
2.5 kHz
7LG32-6AU3
250 / 250
260
2.5 kHz
7LG33-3AU3
300 / 315
330
2.5 kHz
7LG34-1AU3
450 / 400
410
2.5 kHz
7LG34-7AU3
450 / 450
465
2.5 kHz
7LG35-8AU3
600 / 560
575
2.5 kHz
7LG37-4AU3
700 / 710
735
2.5 kHz
7LG38-1AU3
800 / 800
810
2.5 kHz
7LG38-8AU3
900 / 900
910
2.5 kHz
7LG41-0AU3
1000 / 1000
1025
2.5 kHz
7LG41-3AU3
1250 / 1200
1270
2.5 kHz
Commissioning
During commissioning, the dv/dt filter plus Voltage Peak Limiter must be logged on using
STARTER or the AOP30 operator panel (p0230 = 2).
Note
Reset when establishing the factory setting
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.