Operation
6.11 Communication via EtherNet/IP
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
415
Integrating the drive into the EtherNet/IP network via interface X1400 on the CBE20
Proceed as follows to integrate the drive into EtherNet/IP:
1.
Set p8944 (CBE2x DHCP mode) = 2 or 3.
Parameterization Meaning
p8944 = 2
The DHCP server assigns the IP address based on the MAC address.
p8944 = 3
The DHCP server assigns the IP address based on the station name.
2.
Save the settings with p8945 = 2.
The next time that it is run-up, the drive retrieves the IP address made available by a
DHCP server. After the drive has run-up, you can address the drive as Ethernet
participant.
Note
Immediate switchover without restart
The switchover to DHCP is performed immediately and without a restart if the change is
carried out with the EIP command "Set Attribute Single" (class F5 hex, attribute 3), e.g.
using:
•
An EIP control
•
An EIP commissioning tool
Displays:
●
r8950: Station name of interface X1400 at the CBE20
●
r8954: DHCP mode of interface X1400 at the CBE20
●
r8955: MAC address of interface X1400 at the CBE20
6.11.6
Parameters, faults and alarms
Parameters
•
p0978
List of drive objects
•
p0922
IF1 PROFIdrive PZD telegram selection
•
p0999[0...99] List of modified parameters 10
•
p8835
CBE20 firmware selection
•
p8842
COMM BOARD activate send configuration
•
p8920[0...239] PN name of station
•
p8921[0...3] PN IP address
•
p8922[0...3] PN default gateway
•
p8923[0...3] PN Subnet Mask