Output terminals
8.2 Analog outputs
Enclosed Drives
494
Operating Instructions, 12/2018, A5E36652151A
Signals for the analog outputs, object A_INF
Table 8- 3
List of signals for the analog outputs - object A_INF
Signal
Parameter
Unit
Scaling (100% =...)
See table below
Output current
r0068
Arms
p2002
DC link voltage
r0070
V
p2001
Modulation depth
r0074
%
Reference modulation depth
Torque-generating current setpoint
r0077
A
p2002
Torque-generating actual current
r0078
A
p2002
Output power
r0082
kW
r2004
Normalization for object A_INF
Table 8- 4
Normalization for object A_INF
Variable
Scaling parameter
Default for quick commissioning
Reference frequency
100% = p2000
p2000 = p0211
Reference voltage
100% = p2001
p2001 = r0206/r0207
Reference current
100% = p2002
p2002 = r0207
Reference power
100% = r2004
r2004 = r0206
Reference modulation depth 100% = Maximum output voltage without
overload
Reference temperature
100% = p2006
p2006 = 100°C