Electrical installation
4.9 Additional connections
Enclosed Drives
122
Operating Instructions, 12/2018, A5E36652151A
NOTICE
Damage to the dv/dt filter if it is not activated during commissioning
The dv/dt filter may be damaged if it is not activated during commissioning.
•
Activate the dv/dt filter during commissioning using parameter p0230 = 2.
NOTICE
Damage to the dv/dt filter if a motor is not connected
dv/dt filters which are operated without a motor being connected can be damaged or
destroyed.
•
Never operate a dv/dt filter connected to the Motor Module without a connected motor.
Note
Setting pulse frequencies
It is permissible to set pulse frequencies in the range between the rated pulse frequency and
the relevant maximum pulse frequency when a dv/dt filter plus Voltage Peak Limiter is used.
When so doing, take into account the "Current derating as a function of the pulse frequency;
see Technical data.
Table 4- 31 Max. pulse frequency when a dv/dt filter plus Voltage Peak Limiter is used in units with a rated pulse
frequency of 2 kHz
Article no.
6SL3710-...
Unit rating
[HP / kW]
Output current for a pulse
frequency of 2 kHz [A]
Max. pulse frequency when a dv/dt filter
plus Voltage Peak Limiter is used
Supply voltage 3-phase 380 ... 480 V AC
7LE32-1AU3
150 / 110
210
4 kHz
7LE32-6AU3
200 / 132
260
4 kHz
7LE33-1AU3
250 / 160
310
4 kHz
7LE33-8AU3
300 / 200
380
4 kHz
7LE35-0AU3
400 / 250
490
4 kHz