Operation
6.9 Communication via PROFINET IO
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
383
PROFIenergy control commands
Control command
Description
START_Pause
Switches from the operating state to the energy-saving mode
depending on the pause duration.
Switches from the energy-saving mode to the operating state
depending on the pause duration.
START_Pause_with_time_response Switches from the operating state to the energy-saving mode
and also specifies the transition times in the command
response.
END_Pause
Switches from the energy-saving mode to the operating state.
Cancels a switch from the operating state to the energy-saving
mode.
PROFIenergy query commands
Query command
Description
List_Energy_Saving_Modes
Determines all supported energy-saving modes.
Get_Mode
Determines the energy-saving mode.
PEM_Status
Determines the current PROFIenergy status.
PEM_Status_with_CTTO
Determines the actual PROFIenergy status, the same as for
the command "PEM status" and in addition with the regular
transition time to the operating state.
PE_Identify
Determines the supported PROFIenergy commands.
Query_Version
Shows the implemented PROFIenergy profile.
Get_Measurement_List
This command returns the measured value IDs that can be
accessed using the "Get_Measurement_Values" command.
Get_Measurement_List_with_object
_number
This command returns the measured value IDs and the
associated object number that can be accessed using the
"Get_Measurement_Values_with_object_number" command.
Get_Measurement_Values
The command returns the requested measured value using the
measured value ID:
•
For power measured values:
The command addresses the sum of the measured value over
all control drive objects.
•
For energy measured values:
The command returns the sum of the measured value over all
control drive objects.
•
For power factors:
This measured value is supported only for a SINAMICS with a
control drive object.
Get_Measurement_Values_with_
object_number
This command returns the requested measured values using
the measured value ID and the object number. The object
number corresponds to the drive object ID.
The drive object ID of the Control Unit is used to address the
measured values as with "Get_Measurement_Value".