Functions, monitoring and protective functions
9.3 Drive functions
Enclosed Drives
510
Operating Instructions, 12/2018, A5E36652151A
When commissioning induction machines, you are advised to proceed as follows:
●
Before connecting the load, a complete "rotating measurement" (without encoder:
p1960 = 1; with encoder: p1960 = 2) should be carried out. Since the induction machine
is idling, you can expect highly accurate results for the saturation characteristic and the
rated magnetization current.
●
When the load is connected, speed controller optimization should be repeated because
the total moment of inertia has changed. This is realized by selecting parameter p1960
(without encoder: p1960 = 3; with encoder: p1960 = 4).
The saturation characteristic recording is automatically deactivated in parameter p1959
during the speed tuning run.
When permanent-magnet synchronous motors are commissioned, the speed controller
should be tuned (p1900 = 3 or p1960 > 0) when the load is connected.
Carrying out the rotating measurement (p1960 > 0)
The following measurements are carried out when the enable signals are set and a switch-
on command is issued in accordance with the settings in p1959 and p1960.
●
Encoder test
If a speed encoder is used, the direction of rotation and the pulse number are checked.
●
Only for induction motors:
–
Measurement of the magnetization characteristic (p0362 to p0369)
–
Measurement of the magnetization current (p0320) and determination of the offset
voltage of the converter for offset compensation
–
Measurement of the saturation of the leakage inductance and setting of the current
controller adaptation (p0391 to p0393)
This is automatically activated with 1LA1 and 1LA8 motors (p0300 = 11, 18)
(see p1959.5).
●
Speed controller optimization
–
p1470 and p1472, when p1960 = 1 (operation without encoder)
–
p1460 and p1462, when p1960 = 2 (operation with encoder)
–
Kp adaptation switch-off
●
Acceleration precontrol setting (p1496, p1517)
●
Setting for ratio between the total moment of inertia and that of the motor (p0342)
Note
Non-volatile saving
To set the new controller setting permanently, the data must be saved with p0977 or p0971
in a non-volatile memory.