Electrical installation
4.8 Signal connections
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
93
Note
Ensuring the function of digital inputs
An open input is interpreted as "low".
To enable the digital inputs (DI) to function, terminal M2 must be connected.
This is achieved through one of the following measures:
1.
Provision of the ground reference of the digital inputs.
2.
A jumper to terminal M. (Note: This removes the electrical isolation for these digital
inputs.)
Note
If the 24 V supply is briefly interrupted, then the digital outputs are deactivated during this
time.