Operation
6.6 Control via the operator panel
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
303
Normalization for object A_INF
Table 6- 8
Normalization for object A_INF
Variable
Scaling parameter
Default for quick commis-
sioning
Reference frequency
100% = p2000
p2000 = p0211
Reference voltage
100% = p2001
p2001 = r0206/r0207
Reference current
100% = p2002
p2002 = r0207
Reference power
100% = r2004
r2004 = r0206
Reference modulation depth
100% = Maximum output voltage without overload
Reference temperature
100% = p2006
p2006 = 100°C
TM31 object
Table 6- 9
List of signals for the operation screen – TM31 object
Signal
Parameter
Short name
Unit
Scaling
(100% = ...)
Analog input 0 [V, mA]
r4052[0]
AI_UI
V, mA
V: 100 V / mA: 100 mA
Analog input 1 [V, mA]
r4052[1]
AI_UI
V, mA
V: 100 V / mA: 100 mA
Analog input 0, scaled
r4055[0]
AI_%
%
as set in p200x
Analog input 1, scaled
r4055[1]
AI_%
%
as set in p200x
Curve recorder settings
In this menu, the following settings can be made:
Parameter selection
You can select here the parameter whose signal is to be displayed in the form of a trend
curve in the curve recorder.
Interpolation (factory setting: No), serves for the better display of rapidly changing quantities.
●
No: Only the measured values are displayed as points, without a connecting line between
the points.
●
1: The measured values are connected with a vertical line.
●
2: The measured values are connected with a line, offset at the center.
Time base (factory setting: 2 minutes/screen)
The rate of the signal acquisition in minutes per screen is set. The value can be changed in
integer multiples of 2. If an odd value is entered, the value will be rounded up. After changing
the time basis the recording is started again.